HT/LT Substation Transformer, Diversity & DG Sizing Engine

Accurately size 11kV/433V step-down transformers, full-load amps, fault level capacity, and secondary Air Circuit Breakers (ACB) based on empirical diversity factors.

IS:2026 • IS:1180 • CEA Regulations

HT/LT Substation Transformer & DG Sizing Engine

Computes maximum demand with diversity, sizes step-down transformers, full-load amps, fault level, and backup DG capacity.

Selected: 500 kVA Substation
HVAC & Chillers
Lighting (Internal & Ext.)
Small Power & Raw Power
Fire & Plumbing Pumps
Lifts & Elevators
IT / Server / UPS
Total Connected Electrical Load:450 kW
0.75
0.95
20%
Substation Equipment Sizing
Recommended Oil-Cooled / Dry-Type Transformer
500 kVA(11 kV / 433V Step-Down)
✓ Accommodates Max Demand 355 kVA + 20% Expansion Margin
Secondary Full Load Amps696 AmpsAt 415V 3-Phase 50 Hz
LT Main Incomer ACB800A 4-Pole50 kA / 65 kA Breaking Capacity
Secondary Fault Level (I_sc)14.6 kABased on %Z = 4.75%
Recommended DG Backup500 kVA DG SetFor Essential + Fire Loads
Sizing Equations:
Max Demand = 450 kW × 0.75 = 337.5 kW (355.3 kVA)
Send Substation Scope on WhatsApp →
Electrical Authority Guidelines

Substation Engineering Standards

Central Electricity Authority (CEA) norms and Indian Standard specifications.

Empirical Diversity Factors

Not all connected loads operate simultaneously. CPWD guidelines mandate diversity factors between 0.70 and 0.80 for commercial IT buildings to avoid expensive over-sizing of transformers.

Percentage Impedance (%Z)

IS:2026 specifies %Z typically at 4.75% to 5.0% for transformers up to 1000 kVA, and 6.25% for 1250 kVA and above, determining the symmetrical short-circuit current that switchgear must withstand.

DG Set Step-Load Acceptance

When sizing diesel generators, ensure the engine can take a minimum 60% block step load when large chiller motors or fire pumps start up without suffering voltage dip beyond 15%.