Fire Hydrant & Sprinkler Hazen-Williams Hydraulic Sizing Engine
Accurately evaluate friction pressure losses, verify minimum statutory residual pressure at remotest landing valves (≥ 3.5 kg/cm²), and size primary fire pump motor kW.
Design Standards & Compliance Guidelines
Key statutory thresholds mandated by the National Building Code of India and Delhi Fire Service.
Clause 5.1 of NBC 2016 mandates that the running pressure at the remotest outlet shall not be less than 3.5 kg/cm² (3.5 Bar) and shall not exceed 7.0 kg/cm² to prevent hose kickback.
Water velocity in fire main risers should not exceed 2.5 to 3.0 m/s during continuous design discharge to prevent internal pipe wall erosion and water hammer damage.
As per IS:15105, standard pendant and upright sprinklers cover a maximum area of 12 m² per head for Ordinary Hazard, with a maximum distance of 4.0m between heads.