LT Power Cable Sizing, Derating & Voltage Drop Sizing Engine
Accurately calculate derated current capacity, percentage voltage loss across long runs, and optimum cross-sectional conductors for power and lighting sub-feeders.
Cable Sizing & Permissible Voltage Drops
Statutory compliance thresholds mandated by the Central Electricity Authority (CEA) and BS:7671.
Excessive voltage drop in lighting circuits leads to luminaire flickering, LED driver overheating, and premature lamp failure. Maximum permissible drop is strictly 3.0%.
For motor circuits and general power distribution, total steady-state drop from transformer terminal to equipment load terminal shall not exceed 5.0% to ensure rated motor torque.
IS:7098 tables assume 40°C in air. In Delhi NCR, summer temperatures frequently reach 45°C–48°C. A thermal derating multiplier of 0.88 to 0.90 must always be factored in.